Transient Stability Assessment of the Nigerian 330kV Network.
Anthony O Ibe, Ameze Odia
Pages - 357 - 367 | Revised - 30-11-2010 | Published - 20-12-2010
Published in International Journal of Engineering (IJE)
MORE INFORMATION
KEYWORDS
Power (angle) stability limit, , voltage stability limit, , synchronism, Power System
ABSTRACT
Transient stability limit of the Nigerian 330kV power system was assessed in terms of its ability to maintain synchronism among the generating units. The Power (angle) stability limit and voltage stability limit, before, during and after system changes or disturbances were also assessed. The 330kV transmission network was analyzed using the Runge Kutta Method to determine the critical clearing angle and the corresponding critical clearing time. It was observed that a critical clearing angle of 12.85 ͦ with critical clearing time of 0.1s gave a more stable result than a critical clearing angle of 166.376 ͦ with a corresponding critical clearing time of 0.363s. It was therefore recommended that faults on the network be cleared as quickly as possible so as to maintain the system stability.
(Key words: Power (angle) stability limit, voltage stability limit, synchronism)
1 | Google Scholar |
2 | CiteSeerX |
3 | Socol@r |
4 | ResearchGATE |
5 | Libsearch |
6 | Scribd |
7 | SlideShare |
8 | PdfSR |
9 | PDFCAST |
A.O.Ibe ‘ Power Systems Analysis’ Odus press 2002 | |
C. Eze Focus: ‘Power Outage Paralyses Operations at MM Airport’. thisday Online, [internet] 10th May. Available at: http://www.thisdayonline.com/nview.php?id=172968]. 2010 | |
C. Okonji. Focus: ‘Weak transmission threatens 6000MW target’. Compass news paper, Online, [internet] 24th June, 2010. | |
C.C Okoro and Achugbu, ‘Contigency Assessment of the Nigerian 330kV power grid’ 2007 Department of Electrical and Electronics Engineering, Faculty of Engineering University of Lagos, Akoka, Lagos, Nigeria. | |
Grid Code, ‘The Grid Code for the Nigeria Electricity Transmission System. ’ Electrical power sector reform Act, version 01.2005. | |
I. A. W. Noor, M. Azah, ‘Transient stability assessment of a power system using probabilistic neural network’ 2008 American Journal of Applied Sciences. | |
J.G. Duncan, Malukutla S. ‘Power system analysis and design’ 4 th edition international student edition, Canada. 2007. | |
J.M Nadon, B.J Gelmine, E.D McLaughlin. ‘Industrial Electricity’ Delmar publishers 5 th edition, pp107.1994 | |
Onohaebi. O. S. (2009) ‘Power Outages in the Nigerian Grid’ Research Journal of applied sciences 4(1): 1-9 | |
Operation Technology Inc, ‘Electrical Transient Analyzer Program (ETAP)’ 2001 | |
P.Kundur, ‘Power System Stability and Control’ Tata McGraw-Hill, New Delhi.1994 | |